Braemer Evap cooling not starting

My Braemer evap cooling is not starting

The panel just reads “preparing to start” but never does.

I’ll be calling the company who installed on Monday, but wanted to see if I can fix it easily.

I’ve turned power to the unit off and on.
I’ve tried to reset the control panel.

Yet nothing happens and “preparing to start” flashes once the unit is turned on.

Has anyone had this happen before?

Comments

  • +3

    This is not cool.

    • Well done. You must have been saving that one for a while

      • +2

        No need to get all hot and bothered.

  • I’ve turned power to the unit off and on.
    I’ve tried to reset the control panel.

    Then unless you want to get on the roof to start poking around, you have done all you can. Call and wait for them to come.

    Has anyone had this happen before?

    FYI

    Preparing to Start
    Whenever you select AUTO mode or COOL in MANUAL mode, the cooler will take a few minutes to start as it fills with water and saturates the cooling pads. The time will be decreased if the tank is full or the cooler has only recently been turned OFF.

    During this time “Preparing to Start” will flash on the display.

    So its either a water issue most likely a stuck value or pump/float issue.

    All of them you'll need to be up on the roof to see what is and isn't happening.